Code Enforcement Officers have issued the following:
OFFICIAL NOTICE NO. 14-4642UB
Street Address or Location: 1302 BOXWOOD DR NW
Contact(s): Birdsong Meadows, LLC c/o John W. Leet
Date Property Inspected: 6/9/2014
Date Notice Issued: 6/16/2014
Violations must be corrected prior to: 8/15/2014
Permit must be obtained by: 7/16/2014
VIOLATIONS |
• Electrical system must meet City Electrical Code as determined by the City of Huntsville Inspection Department. |
• Structure must meet Building Code as determined by the City of Huntsville Inspection Department. |
• Roof sheeting damaged, roof leaking into multiple units on first and second floor.
The structural integrity of the roof has been compromised.
There was no fire separation between units.
Brick support of stair landing was damaged.
Water was puddling on egress paths.
Smoke detectors were missing in units.
The water heaters were not accessible if they needed to be repaired or replaced.
NEC 2002 ART.100.1 Equipment has to be accessible.
The water that leaked had compromised some light fixtures.
NEC 2002 ART.410.10.A Discusses light fixtures being suitable for wetness.
Many open junction were noticed. ART 314.28C, 314.29, 314.7.C,D,E
All deal with junction boxes and accessibility. |
|